| range of product | Modicon X80 |
|---|---|
| product or component type | Analog output module |
| electrical connection | 20 ways 1 connector |
| Isolation between channels | Isolated |
| measurement error | <= 0.2 % of full scale 0...60 °C 0.1 % of full scale 25 °C |
|---|---|
| temperature drift | 30 ppm/°C |
| recalibration | Factory calibrated |
| minimum crosstalk attenuation | 90 dB |
| Common mode rejection | 100 dB |
| isolation voltage | 1400 V DC between channels and ground 1400 V DC between channels and bus 750 V DC between channels |
| detection type | Open circuit 0...20 mA Open circuit 4...20 mA Short circuit +/- 10 V |
| load impedance ohmic | <= 600 Ohm 0...20 mA <= 600 Ohm 4...20 mA >= 1000 Ohm +/- 10 V |
| output level | High level |
| analogue output number | 2 |
| analogue output type | Current: 0...20 mA Current: 4...20 mA Voltage: +/- 10 V |
| analogue output resolution | 15 bits + sign |
| supply | Internal power supply via rack |
| conversion time | <= 1 ms |
| maximum conversion value | +/- 11.25 V +/- 10 V 0...24 mA 0...20 mA 0...24 mA 4...20 mA |
| fallback mode | Predefined Configurable |
| operating altitude | 0...2000 m 2000...5000 m with derating factor |
| status LED | 1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O |
| net weight | 0.144 kg |
| power consumption in W | 2.1 W 24 V DC typical 2.8 W 24 V DC maximum 0.35 W 3.3 V DC typical 0.48 W 3.3 V DC maximum |
| vibration resistance | 3 gn |
|---|---|
| shock resistance | 30 gn |
| ambient air temperature for storage | -40…85 °C |
| ambient air temperature for operation | 0…60 °C |
| relative humidity | 5…95 % at 55 °C without condensation |
| IP degree of protection | IP20 |
| directives | 2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility |
| product certifications | CE RCM CSA EAC Merchant Navy UL |
| standards | EN/IEC 61010-2-201 EN/IEC 61131-2 UL 61010-2-201 CSA C22.2 No 61010-2-201 |