Description

TeSys GV motor circuit breaker, 3 poles (3P), 10A/690V, for 3-phase motor applications 3-4kW@400V. It provides a thermal-magnetic protection with a thermal setting range 6-10A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).


Specifications


Main
RangeTeSys Deca
Product nameTeSys GV2
Product or component typeMotor circuit breaker
Device short nameGV2ME
Device applicationMotor protection
Trip unit technologyThermal-magnetic

Complementary
Poles description3P
Network typeAC
Utilisation categoryCategory A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1
Network frequency50/60 Hz conforming to IEC 60947-2
Motor power kW3 kW at 400/415 V AC 50/60 Hz
4 kW at 400/415 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
5.5 kW at 690 V AC 50/60 Hz
7.5 kW at 690 V AC 50/60 Hz
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control typePush-button
[In] rated current10 A
Thermal protection adjustment range6…10 A conforming to IEC 60947-2
Magnetic tripping current149 A
[Ith] conventional free air thermal current10 A conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Phase failure sensitivityYes conforming to IEC 60947-4-1
Suitability for isolationYes conforming to IEC 60947-1
Power dissipation per pole2.5 W
Mechanical durability100000 cycles
Electrical durability100000 cycles for AC-3 at 415 V In
100000 cycles for AC-3e at 415 V In
Rated dutyUninterrupted conforming to IEC 60947-4-1
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid
Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
Tightening torque1.7 N.m - on screw clamp terminal
Fixing mode35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
Mounting positionHorizontal
Vertical
Width45 mm
Height89 mm
Depth78.5 mm
Net weight0.26 kg
ColourDark grey

Environment
StandardsEN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2
Product certificationsCB Scheme
CE
UKCA
CCC
cULus
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
IK degree of protectionIK04
IP degree of protectionIP20 conforming to IEC 60529
Climatic withstandconforming to IACS E10
Ambient air temperature for storage-40…80 °C
Fire resistance960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation-20…60 °C
Mechanical robustnessShocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
Operating altitude<= 2000 m

Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height4.800 cm
Package 1 Width8.600 cm
Package 1 Length9.300 cm
Package 1 Weight274.000 g
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight6.864 kg
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Height75.000 cm
Package 3 Width60.000 cm
Package 3 Length80.000 cm
Package 3 Weight119.000 kg