Square D QBL22125 PowerPacT Q Feed-Thru 240V 125A 2 Pole Circuit Breaker 50/60Hz
PowerPacT Q-Frame circuit breakers are used for overcurrent protection and switching on 240VAC systems. They are rated for 240VAC operational voltage and provide thermal magnetic trip protection. PowerPacT Q circuit breaker is 2-pole unit mount and I-Line constructions. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. This unit has lugs on both the line and load sides. This PowerPacT Q, 125A, 2 pole, circuit breaker has an interrupting rating of 10kA at 208Y/120VAC and 240VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT Q circuit breakers comply to UL, CSA, and NOM standards and are IEC certified.
- PowerPacT Q 125A, 240VAC 2 poles unit mount molded case circuit breaker.
- Designed for overcurrent protection and switching on AC systems.
- PowerPacT Q circuit breakers contain thermal (overload) and magnetic (short circuit) sensing elements in each pole
- Breaker has interrupting ratings (AIR) of 10kA 240 VAC and has 80% rating
- Main applications are Industrial markets and OEM Commercial
- Range: PowerPact
- Product name: PowerPact Q
- Product or Component Type: Circuit breaker
- Device Application: Distribution
- Line Rated Current: 125 A
- Number of Poles: 2P
- Control Type: Operating handle
- Breaking capacity code: B
- Breaking capacity: 10 kA 120/208 V AC 50/60 Hz UL; 10 kA 240 V AC 50/60 Hz UL
- [Ue] rated operational voltage: 240 V AC 50/60 Hz UL
- Network Frequency: 50/60 Hz
- [Uimp] rated impulse withstand voltage: 8 kV UL
- Trip unit technology: Thermal-magnetic
- Magnetic tripping current: 2400 A
- Magnetic hold current: 1200 A
- Continuous current rating: 80 %
- Utilisation category: Category A
- Mechanical durability: 1000 cycles loaded; 5000 cycles no load
- Local signaling: 1 trip indicator green
- Mounting mode: Unit mount lug
- Mounting Support: Lug
- Electrical connection: Lugs, load; Lugs, line
- Tightening torque: 247.8 lbf.in (28 N.m) 0.04…0.2 in² (25…150 mm²) (AWG 4...300 kcmil)
- Power wire stripping length: 0.9 in (22 mm)
- Height: 6.47 in (164.34 mm)
- Width: 3 in (76.2 mm)
- Depth: 3.93 in (99.82 mm)
- Circuit breaker application: HACR rated