The Honeywell XNX-UTSE-RNNNN is a universal transmitter designed to work with various sensors on a single platform. It allows for easy integration and reliable functionality. This product is suitable for use with gas monitoring controllers and industry-standard PLCs. The transmitter is equipped with HART EDDL software, enabling quick assessments of the health status of gas detectors.
- Compatible with a range of sensors on one platform.
- Provides flexible input and output options.
- Includes a large backlit LCD display with sensory indicators.
Product Highlights
The Honeywell XNX-UTSE-RNNNN is designed for effective gas detection and monitoring. With straightforward installation and maintenance, it is perfect for professionals in HVAC and gas monitoring applications.
Product Information
Standard Information
- Operating Voltage EC/mV: 16V to 32V (24V nominal)
- Operating Voltage IR: 18V to 32V (24V nominal)
Technical Specifications
- Power Consumption XNX EC: 6.2W
- Power Consumption XNX mV: 6.5W
- Power Consumption XNX IR (Optima): 9.7W
- Power Consumption XNX IR (Excel): 13.2W
- Inrush XNX EC: <1A, <10ms@24VDC
- Termination: Crimp style pluggable with retaining screws, 12-28 AWG
- Signal Standard: HART over 3-wire 4-20 mA
- Cable Ports: 5 - Available in 3/4inch NPT, or M25
- User Interface: Custom Backlit LCD, magnetic wand operation
- IP Rating: IP66
- Temperature Range: -40°C to +65°C
- Humidity: 0 to 99% RH non-condensing
- Pressure: 80 kPa to 120 kPa
- Relays Type: 3 form inchCinch SPCO contacts for alarms
- Modbus Baud rates: 1200 to 38,400
- Dimensional Weight: 5 lbs
- Dimensions: 6.138 x 7.75 x 4.48 inches