Dust and drip proof construction. (designed to IEC 60529 IP54).
|
|
Designed to meet IEC 61010-1 and IEC 61557 safety standard.
|
|
1mA rated test current at the minimum resistance.
|
|
200mA measuring current on continuity testing.
|
|
Automatic discharge of circuit capacitance.(Any charge stored in the circuit under test will be automatically discharged after testing.).
|
|
Live circuit warning buzzer and neon lamp.
|
|
Small and lightweight. Shock resistant new case material.
|
|
AC voltmeter with linear, easy-to-read scale.
|
|
Operates on AA, R6P×6 dry batteries.
|
|
|
Insulation Resistance
|
|
Test Voltage
|
250V/500V/1000V
|
|
Measuring Ranges
(Mid-scale Value)
|
100MΩ/200MΩ/400MΩ
(1MΩ) (2MΩ) (4MΩ)
|
|
Output Voltage
on open circuit
|
Rated test voltage+20%, -0%
|
|
Nominal Current
|
1mA DC min.
|
|
Output Short
Circuit Current
|
1~2mA DC
|
|
Accuracy
|
0.1~10MΩ/0.2~20MΩ/0.4~40MΩ
(Accuracy Guaranteed Ranges) ±5% of indicated value
|
|
Continuity
|
|
Measuring Ranges
(Mid-scale Value)
|
3Ω/500Ω
(1.5Ω) / (20Ω)
|
|
Output Voltage
on open circuit
|
4.1V DC approx.
|
|
Measuring Current
|
210mA DC min.
|
|
Accuracy
|
|±1.5% of scale length
|
|
AC Voltage
|
|
AC Voltage
|
0~600V AC
|
|
Accuracy
|
|±5% of scale length
|
|
General
|
|
Safety Standard
|
IEC 61010-1 CAT.III 600V Pollution Degree 2
IEC 61010-2-031
IEC 61557-1/2/4
|
|
IP Rating
|
IEC 60529-IP54
|
|
EMC Standard
|
IEC 61326-1
|
|
Withstand Voltage
|
3700V AC for 1 minute
|
|
Power Source
|
R6P (AA) (1.5V) × 6
|
|
Dimensions
|
106(L) × 160(W) × 72(D)mm
|
|
Weight
|
560g approx.
|
|
Accessories
|
(Test leads) Pouch for test leads
8923 (F500mA/600V fuse) × 2
R6P (AA) × 6
Shoulder Strap
Instruction Manual
|
|
|
Notice:
Because,the international air shipping forbid to ship liquid,powder and batteries, If you purchased goods containing such items, we will not be putting them packing. Thank you for your support.
|