Landis & Gyr LFL1.322-F Burner Control Box 220-240V Serie 02 Gas Oil Programmer

Burner Control Unit · Like New

Landis & Gyr
LFL1.322-F

Gas & Dual-Fuel Burner Control Box · 220-240V · tv 36s / ts 2s

Landis & Gyr LFL1.322-F Serie 02 automatic burner control box for medium to high capacity forced draught gas, oil, or dual-fuel burners.

✅ EU Compliant

DIN-DVGW Reg. Nr. 82.05 b LG · DIN Rg. 11869/82 · ATG C31-21 62BE · +S

Combustion Management

Fully Automated
Burner Sequence Control

The LFL1.322-F manages and supervises forced draught gas and dual-fuel burners in multistage or modulating operation. It executes a precise 36-second prepurge cycle and 2-second safety ignition interval while continuously monitoring the flame via ionization probe or UV detector.

Product Details

At a glance.

Product Information

Brand

Landis & Gyr

Model / MPN

LFL1.322-F

Series

Serie 02

Condition

Like New

Manufacturer Warranty

1 Year (to be verified)

Dimensions

123 x 103 x 120 mm (to be verified)

Material

Flame-retardant plastic housing

Date Code

9228

Key Features & Benefits

Key
features.

🏭

Exact OEM Specification

Direct drop-in replacement

Factory-built LFL1.322-F Serie 02 controller directly replaces existing modular control units on compatible burner baseplates without rewiring.

Integrated Cycle Indicator

Instant visual operational status

Built-in mechanical sequence dial visible through top inspection window shows real-time program position and lockout diagnosis.

Dual-Flame Sensing Support

Flexible detection methods

Compatible with ionization sensors as well as optical UV flame detectors such as QRA2 and QRA10 probes.

Precise Timing Controls

Compliant ignition sequencing

Calibrated 36-second prepurge period and 2-second safety lockout period ensure complete chamber ventilation and safe light-off.

🛡️

Certified Safety Engineering

Standardized gas appliance compliance

Certified under DIN-DVGW registration 82.05 b LG and ATG regulations for commercial and industrial heating installations.

Technical Data

Detailed Specifications.

Supply Voltage 220-240V AC
Mains Frequency 50-60 Hz
Power Consumption 3.5 VA
Prepurge Time (tv) 36 s
Safety Time (ts) 2 s
Pre-ignition Time (tvn) 2 s
Contact Rating (Individual) 4 A
Contact Rating (Total) 5 A
Series Serie 02
Flame Detector Compatibility QRA2, QRA10, Ionization probe
Operating Temperature Range -20 to +60 °C (to be verified)
⚠️ To be verified
Enclosure Protection IP40 (to be verified)
⚠️ To be verified
Burner Capacity Type Medium to large capacity
Application Gas, oil, or dual-fuel forced draught burners
Operation Mode Multistage or modulating

Applications & Compatibility

Where it excels.

Forced draught gas burner sequence control
Dual-fuel modulating industrial heating systems
Replacement of worn LFL1.322 control units on existing boilers
Multi-stage industrial air heater burner management

⚠️ Not suitable for

Installation by non-qualified persons (gas and electrical safety regulations)
Low-voltage 24V or 12V DC burner applications
Atmospheric residential gas water heaters without forced draft

Landis Gyr LFL1.322-F · LFL1.322-F burner control box · Landis Staefa LFL1 322 · Siemens LFL1.322 gas programmer · forced draught burner controller 230V · LFL1.322 Serie 02 · Landis Gyr combustion controller · Feuerungsautomat LFL1.322-F · Gasfeuerungsautomat Landis Gyr · coffret de securite LFL1.322-F