| Range | VigiPacT |
|---|---|
| Device short name | RH10M |
| Product or component type | Residual current protection relay |
| Relay application | Protection relay |
| Mounting support | DIN rail |
| Earth-leakage protection class | Type A |
| Type of setting | None |
| Residual earth-leakage sensitity adjustment type | Fixed |
| Earth-leakage sensitivity | 0.3 A |
| Earth-leakage time delay | Instantaneous |
| Current sensors compatibility | VigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor |
| [Ithe] conventional enclosed thermal current | 8 A |
| Minimum load | 10 mA at 12 V |
| [Us] rated supply voltage | 220...240 V AC 50/60 Hz 55...110 % |
| Power consumption in VA | 4 VA |
| Monitored distribution system | 1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum) |
| Earthing system | TT IT TN-S |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Reset | Manual reset |