DC50D/DC52D MKII Electronic Generator Controller Module Control Panel for Diesel Engine or Generator

The difference between DC50D and DC52D

Based on DC50D, DC52D adds the mains monitoring and mains/generation automatic switching control (AMF) function to the single-machine automation system consisting of one generator unit.

Genset Controller DC5xD Series

This series controller is specialized for Diesel / Gasoline / Gas Genset Start, Stop,Parameters monitoring, faults-checking as well as data setting.

3.5 inch 240*128 colorful LCD screen display with brand new UI design is adapted in this controller that the relative failures can be displayed directly. All the parameters can be displayed by simulated indicators and words.Besides, LCD screen can display various faults in the same time that the genset will be stopped once it can not work smoothly.

There are Chinese/English/ interface options, more language can be set according to user’s request. All the parameters can be configured through the front face buttons or use programmable interface by RS485 or USB to adjust via PC.It can be widely applied for all kinds of auto control system of gensets.

Main Features:

  • 32 units Micro-procession technology is used.
  • 3.5 inch TFT colorful big screen LCD, option language interface(Chinese/English), user’s language set if necessary.
  • Indicator and number display through UI surface.
  • Acrylic material is adapted to protect the screen.
  • Silicone panels;
  • USB Port: parameters can be set even without power through USD port to monitor in real time.
  • Various kinds of parameters display.
  • Input/output function, status can be shown directly.
  • More categories of surface setting.
  • Real time clock inside: preset time operate and auto maintenance is available. Genset working plan can be set as per week or month.
  • Three class protection countdown function, which can set the maintenance time or date.
  • Records function: relative faults shall be recorded in real time.
  • Totally 6 relay’s output, among which 4 relay output can be self-configurable, each relay can be set as max 25 functions, besides, there are 4 groups as non-contact terminals.
  • 5 switch value input, and each can be set as max 30 functions.
  • 3 sensor simulation input connectors, 6 input types is configurable and various kinds of units can be set.
  • Battery charging control function,which can protect the battery according to battery voltage status.
  • Sensor can be self-defined by front face button or PC software.
  • Adapt to 3P4W,1P2W,2P3W(120V/240V,50/60HZ)
  • Various of crank conditions(RPM,Frequency, Oil Pressure) can be chosen
  • Control Protection:Auto Start/Stop of genset,load transfer (ATS control) and perfect failure display and protection.
  • Standard water-proof rubber gasket. The waterproof can reach IP54
  • Module design: All the connections are adapted with European connectors so that installation, connection, repair and replacement can be more easily.

Parameters Display:

  • Engine RPM
  • Engine oil pressure
  • Engine water temperature
  • Engine fuel temperature
  • Engine cylinder temperature
  • Engine Tank temperature
  • Engine fuel level
  • Engine battery voltage
  • Charging voltage
  • Mains Frequency (only for DC52D)
  • Mains phase voltage L-N(only for DC52D)
  • Mains phase voltage L-L(only for DC52D)
  • Generator 3 Phase voltage L-N
  • Generator 3 Phase voltage L-L
  • Generator 3 phase current A
  • Generator Frequency Hz
  • Generator Power Factor COSφ
  • Generator active power KW
  • Generator apparent power KVA
  • Generator reactive power KVar
  • Current loading rate %
  • Total average loading rate %
  • Current consumption KWH
  • Total consumption Kwh
  • Total Crank times
  • Current running time
  • Total running time
  • Three classes maintenance notice

Protection:

  • Over speed
  • Under speed
  • Low oil pressure
  • High water temperature
  • High Oil temperature
  • High Cylinder Temperature
  • High Tank temperature
  • Low fuel level
  • Low oil level
  • External emergency alarm
  • D+ Opened
  • RPM Lost
  • Sensor Open
  • Over Frequency
  • Under Frequency
  • Over voltage
  • under voltage
  • over current
  • Non-balance of current
  • Over power
  • Lack of Phase
  • reverse phase sequence
  • Gen load failure
  • Gen unload failure
  • Mains Load failure
  • Mains unload failure
  • Primary maintenance expire
  • Secondary maintenance expire
  • Maintenance expire
  • Low water level alarm
  • Emergency Stop
  • Crank failure
  • Over battery voltage
  • Under Battery voltage
  • Charging failure
  • Battery Charging failure
  • Stop Failure

Parameters:

Options

Parameters

Working voltage

DC8V----36V Continuous

Power consumption

Standby:24V:MAX 1W

Working:24V:MAX 5W

AC Voltage Input

1P2W 30VAC-276VAC(ph-N)

2P3W 30VAC-276VAC(ph-N)

3P4W 30VAC-276VAC(ph-N)

Rotate speed sensor Frequency

200-10000Hz

MAX Accumulating Time

99999.9Hours(Min Store time:6min)

Fuel Relay Output

16Amp DC+VE Supply voltage

Start Relay Output

16Amp DC+VE Supply voltage

Programmable Relay output 1

5Amp DC+VE Supply voltage

Programmable Relay output 2

5AMP Non-contact-Normal open--Normal close output

Programmable Relay output 3

5AMP Non-contact Normal Open output

Programmable Relay output 4

5AMP Non-contact normal open output

Excitation output

Max 1AMP DC+VE supply voltage

Switch value input

Available if connecting with Battery -

Working condition

-20-65℃

Storage condition

-40-85℃

Protection Level

IP54:when waterproof rubber gasket is added between controller and its panel

Overall dimension

210mm*160mm*50mm

Panel cutout

186mm*142mm

Weight

0.9Kg



Warning:

Please don’t move battery during running status or it may cause the controller broken

Package include:
  • 1 x DC5xD Genset Controller
  • 2 x Mounting screws
  • 1 x User Manual​