Features • Industry standard for very low differential pressure • ±0.25%, ±0.4%, ±1% FS accuracy • Up to 10 PSI overpressure (range dependent) • Installation time minimized w/ mounting options • Reverse wiring protection • Internal regulation permits use with unregulated DC power supplies • Fire retardant case (UL 94 V-0 approved) • CE & RoHS compliant
Applications • HVAC/R systems • Room pressurization for critical environments • Energy management systems • Variable air volume and fan control (VAV) • Environmental pollution control • Lab & fume hood control
Thermal effects Compensated range oF (oC) 0 to +150 (-18 to +65) Zero shift %FS/100oF(50oC) ±0.033 (±0.06) Span shift %FS/100oF(50oC) ±0.033 (±0.06) Max. line pressure 10 PSI Overpressure Up to 10 PSI (range dependent) Long term stability 0.5% FS/YR
Environmental data Operating temperature oF (oC)3 0 to +175 (-18 to +79) Storage temperature oF (oC) -65 to +250 (-54 to +121)
Position effect Range / Zero offset (%FS/G) 0.1” W.C. 2.3 0.25” W.C. 1 0.5” W.C. 0.5 1.0” W.C. 0.3 2.5” W.C. 0.2 10” W.C. 0.15
Physical description Case Fire-retardant glass filled polyester (UL 94 V-O Approved) Electrical Connection Screw terminal strip Mounting 4 screw holes on removable zinc plated steel base (designed for 2.75” snap track) Pressure Fittings 3/16” O.D. barbed brass for 1/4” push on tubing Zero and Span Adjustments Accessible on top of case Weight (approx.) 10 Ounces
Electrical data (voltage) Circuit 3-Wire (Com, Out, Exc) Excitation/output5 9 to 30 VDC / 0 to 5 VDC6,7 Output impedance 100 ohms Bidirectional output at zero pressure 2.5 VDC6,7
Electrical data (current) Circuit 2-wire Output8 4 to 20 mA9,10 External load 0 to 800 ohms Min. loop supply voltage (VDC) 9 + 0.02 x (resistance of receiver plus line) Max. loop supply voltage (VDC) 30 + 0.004 x (resistance of receiver plus line) Bidirectional output at zero pressure 12 mA9,10
Pressure media Clean air or similar non-conducting gases.