Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 3000VA 2250W, RM, 2U, 120V, 30A
Condition: New batteries, refurbished UPS
Part Number: SMART3000RM2U
Maximum output: 2250W / 3000VA
Typical backup time at half load: 10 minutes (1125 Watts)
Typical backup time at full load: 3 minutes (2250 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 3000VA 2250W RM 120V SMART3000RM2U Manual
SMART3000RM2U - Tripp Lite SmartPro 3000VA Specifications:
Input:
|
Rated input current (Maximum Load) |
24A |
||
|
Nominal Input Voltage(s) Supported |
120V AC |
||
|
UPS Input Connection Type |
|
||
|
UPS Input Cord Length (ft.) |
10 |
||
|
UPS Input Cord Length (m) |
3.1 |
||
|
Recommended Electrical Service |
30A 120V |
||
|
Input Phase |
Single-Phase |
Output:
|
Output Volt Amp Capacity (VA) |
3000 |
||||
|
Output Capacity (kVA) |
3.0 |
||||
|
Output Watt Capacity (Watts) |
2250 |
||||
|
Output kW Capacity (kW) |
2.25 |
||||
|
Output Capacity Details |
Output is reduced to 1600 watts maximum when used with external battery packs |
||||
|
Power Factor |
0.75 |
||||
|
Nominal Voltage Details |
120v nominal output in battery mode |
||||
|
Frequency Compatibility |
60 Hz |
||||
|
Output Voltage Regulation (Line Mode) |
-14%, +6% |
||||
|
Output Voltage Regulation (Battery Mode) |
+/- 5% |
||||
|
Load Management Receptacles |
Two switchable single-outlet load banks |
||||
|
Output Circuit Breakers |
Two 20A output breakers protect 4 5-15/20R outlets each |
||||
|
Output AC Waveform (AC Mode) |
Pure Sine wave |
||||
|
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||||
|
Nominal Output Voltage(s) Supported |
110V; 115V; 120V |
||||
|
Output Receptacles |
|
||||
|
Individually Controllable Load Banks |
Yes |
Battery:
|
Battery Type |
Valve Regulated Lead Acid (VRLA) |
|
Full Load Runtime (min.) |
3.5 min. (2250w) |
|
Half Load Runtime (min.) |
10 min. (1125w) |
|
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
|
Expandable Runtime |
Yes |
|
External Battery Pack Compatibility |
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27- 2US (multi-pack compatible) |
|
DC System Voltage (VDC) |
48 |
|
Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% |
|
Battery Access |
Front panel battery access door |
|
Internal UPS Replacement Battery Cartridge |
RBC94-2U |
|
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Voltage Regulation:
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145 |
|
Overvoltage Correction |
Input voltages between 127 and 145 are reduced by 12% |
|
Undervoltage Correction |
Input voltages between 108 and 96 are boosted by 12% |
|
Severe Undervoltage Correction |
Input voltages between 83 and 95 are boosted by 24% |
User Interface, Alerts & Controls:
|
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
|
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
|
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
|
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
Surge / Noise Suppression:
|
UPS AC Suppression Joule Rating |
570 |
|
UPS AC Suppression Response Time |
Instantaneous |
|
EMI / RFI AC Noise Suppression |
Yes |
Physical:
|
Primary Form Factor |
Rackmount
|
|
Cooling Method |
Fan
|
|
Mounting Accessory Description |
4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm) - Not included
|
|
Installation Form Factors Supported: |
4 post 19 inch rackmount & 2 post
|
|
Installation Form Factors Supported with Optional Accessories |
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2- 9USTAND ); Wallmount ( 2POSTRMKITWM )
|
|
Minimum Required Rack Depth with External Battery Pack (cm) |
67
|
|
Minimum Required Rack Depth with External Battery Pack (in.) |
26.5
|
|
Minimum Required Rack Depth without External Battery Pack (cm.) |
62
|
|
Minimum Required Rack Depth without External Battery Pack (in.) |
24.5
|
|
Optional Mounting Accessory Notes |
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
|
|
Primary UPS Depth (mm) |
494
|
|
Primary UPS Height (mm) |
87 |
|
Primary UPS Width (mm) |
440 |
|
Rack Height |
2U |
|
Shipping Dimensions (hwd / cm) |
21.34 x 60.45 x 55.12 |
|
Shipping Dimensions (hwd / in.) |
8.40 x 23.80 x 21.70 |
|
Shipping Weight (kg) |
37.19 |
|
Shipping Weight (lbs.) |
82.00 |
|
UPS Housing Material |
Steel |
|
UPS Power Module Dimensions (hwd, cm) |
8.71 x 43.99 x 49.43 |
|
UPS Power Module Dimensions (hwd, in.) |
3.43 x 17.32 x 19.46 |
|
UPS Power Module Weight (kg) |
28.49 |
|
UPS Power Module Weight (lbs.) |
62.8 |
Environmental:
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
|
Relative Humidity |
0 to 95%, non-condensing |
|
AC Mode BTU / Hr. (Full Load) |
189 |
|
Battery Mode BTU / Hr. (Full Load) |
1356 |
|
AC Mode Efficiency Rating (100% Load) |
98% |
|
Audible Noise |
45 dBA maximum, front side 1m |
Communications:
|
Network Management Cards |
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; RELAYIOCARD
|
|
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
|
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert |
|
Communications Cable |
USB and DB9 cabling included |
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
Network UPS Tools Compatibility |
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite |
|
Network Management Card Description |
Network management card optional |
|
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |