This listing is for Repair and testing of your 171986 or 238892 board
This board controls the wire feed DC motor.
We will repair as required, and final test with DC motor using the normal control connections to verify proper operation.

Please message me about troubleshooting questions
Below is a list of things that also need to work for the wire feed to function.

1. Verify that wire feed motor works by applying 12V dc to it.
2. There must be 24 VAC or similar AC voltage present at terminal 1-3 of the PCB when welder is turned on.
3. 1K speed potentiometer should be checked to verify resistance changes at the wiper as it is turned
4. Should hear relay CR1 click when trigger is pressed. The Normally Open contacts should then close.
5. Plug PLG3 must be connected on RC3 to connect pins 1-2 on RC3 if spoolmate option is not present.
6. If spoolmate option is installed, then it needs to be properly plugged in and switch working.

If you are confident that these are all good, then send the board to us for repair.

After payment, send your board along with contact information to:

Berg Controls, LLC
10998 County Road 24
New Ulm, MN 56073

Free return USPS shipping after repair.
6 month warranty.
If, for some reason it is unrepairable, we will refund your payment and return it to you.